Extinguisher Coverage Area

Pick the extinguisher rating + hazard class. We return the max area one unit can protect per NFPA 10 tables.

NFPA 10 Table 6.2.1.1 (Class A)

RatingLight hazardOrdinaryExtra hazard
1-A3,000 sf
2-A6,000 sf3,000 sf
3-A9,000 sf4,500 sf3,000 sf
4-A11,250 sf6,000 sf4,000 sf
6-A11,250 sf9,000 sf6,000 sf
10-A11,250 sf11,250 sf10,000 sf
20-A11,250 sf11,250 sf11,250 sf
40-A11,250 sf11,250 sf11,250 sf

Maximum protected area is capped at 11,250 sf per extinguisher regardless of rating. Travel distance still controls (max 75 ft for Class A).

FAQ

Why two different limits? +
The coverage table is one constraint. The 75 ft max travel distance is another. Both must be satisfied — whichever requires more extinguishers wins.
What about Class B? +
Class B uses spacing (50 ft light, 30 ft extra), not area. Rating controls hazard intensity, not area covered.