Construction
Wire Size Calculator (NEC)
Sizing electrical wire isn't just about ampacity (the current the wire can carry) — you also need to keep voltage drop under 3% for any meaningful run, or your equipment runs slow, hot, and inefficient. A 20A circuit at 50 ft uses #12 wire (ampacity is plenty); the same 20A at 150 ft needs #10 wire to keep voltage drop in spec. This calculator runs both checks: NEC ampacity from Table 310.16 (75°C copper or aluminum) PLUS voltage drop limit at 3%, and returns the larger wire (smaller AWG number) of the two. Critical for any electrical install that involves long cable runs.
Minimum AWG
—
- Ampacity limit
- —
- Voltage drop %
- —
- Per NEC + 3% drop
- —
Two sizing checks: ampacity AND voltage drop
Ampacity: the maximum current a wire can carry without overheating, set by NEC Table 310.16. A 20A circuit needs #12 copper minimum; 30A needs #10; 40A needs #8; 50A needs #8 or #6.
Voltage drop: the volts lost in the wire as current flows. NEC recommends (not requires) 3% max on branch circuits, 5% total. Beyond that, motors run hot, electronics misbehave, lights dim. Voltage drop scales with: amperage, length (round-trip), and inverse wire size.
Formula: VD = (2 × K × L × I) / CM, where K = 12.9 (copper) or 21.2 (aluminum), L = one-way distance in feet, I = current in amps, CM = circular mils for the wire size.
Worked example: 20A circuit, 100 ft one-way, 120V, copper. Ampacity says #12 (rated 20A) is enough. Voltage drop check: with #12 (6,530 CM), drop = (2 × 12.9 × 100 × 20) / 6530 = 7.9V = 6.6% drop. Way over 3%. Upsize to #10 (10,380 CM): drop = 5.0V = 4.1%. Still over. #8 (16,510 CM): 3.1V = 2.6%. Use #8 for this run.
When voltage drop dominates over ampacity
For runs under ~50 ft, ampacity usually dominates and the standard wire size for the load works. For longer runs (over 100 ft) or higher loads (over 30A), voltage drop starts dominating and you need to upsize.
- 50-ft, 20A: #12 (ampacity); voltage drop ~3%, just within spec.
- 100-ft, 20A: #10 needed for voltage drop.
- 150-ft, 20A: #8 needed for voltage drop.
- 50-ft, 50A circuit (EV charger): #6 for ampacity; voltage drop check usually passes at #6.
- 200-ft, 30A subpanel feed: #6 minimum, often #4 for voltage drop. Aluminum #2 for cost savings on long runs.
How to use this calculator
- Load in amps: the circuit's current draw.
- One-way distance: from panel to load, in feet.
- System voltage: 120V single-phase (typical receptacle), 240V (heavy appliances, EV chargers), 480V (commercial).
- Conductor: copper (typical) or aluminum (long runs to save cost).
- Output: minimum AWG sized for both ampacity AND 3% voltage drop, plus voltage drop at that gauge.
- Always confirm against NEC and local code — this is a planning tool, not a substitute for a licensed electrician.
Common scenarios
Garage outlet 75 ft from panel, 20A circuit, 120V. #12 ampacity-OK, voltage drop ~5% (over). Upsize to #10: voltage drop 3.1% — just under. Use #10 copper.
EV charger circuit, 50 ft, 50A continuous (62A breaker after 125% rule), 240V copper. #6 copper handles 65A ampacity and 1.6% voltage drop — well within spec. Standard install.
Detached shop subpanel 200 ft from house, 50A 240V copper. Ampacity demands #6 (65A rated). Voltage drop at #6: 2.8% — in spec but tight. Upsize to #4 for safety margin and future load growth.
FAQ
Why 3% voltage drop, not higher? +
Aluminum vs copper wire? +
What's the difference between THHN, NM-B, and UF? +
Do I need a different size wire for ground? +
What does "75°C ampacity" mean? +
Can I add wires in parallel to handle more amps? +
What about derating for ambient temp and bundled wires? +
Should I always upsize for future loads? +
Heads up: ClutchCalcs gives you fast, accurate results — but always sanity-check critical decisions (medical, financial, structural) with a professional.
Spot a wrong number or want a calculator added? Tell us →